system will be designed.
The first
as the pipe slope.
This gives an
sewers to be designed will be the
acceptable velocity in a 4-inch pipe.
house connections using figure 14.
The invert elevation is chosen 2.4
feet below the ground at building B.
a. Building A to manhole (MH) 8.
This gives 2 feet of cover over the 4-
The values are tabulated in row 1 of
inch (approximately .4 feet) sewer.
the data sheet (fig 17).
The ground
The design is tabulated in row 3,
slope of 2 feet in 75 is used as a
figure 17. For the line from building
first try.
With a 4-inch house sewer
C, the ground slope of 1 foot in 30
(the minimum size allowable) a full
was used.
Its design parallels that
flow of 127 gallons per minute is
of building B and is tabulated in row
obtained.
This is less than the
4.
actual
flow
and
therefore
is
unacceptable.
The two choices now
c. Connections to MH 7. The design
available are to increase the slope
of the lateral between MH 8 and MH 7
and keep the 4-inch pipe size, or
is shown in row 5. Note that in this
increase the pipe diameter.
To get a
length of pipe infiltration can no
200 gallons per minute full flow in a
longer be ignored.
A figure of 4
4-inch sewer the slope must be 6.8
gallons per minute per 1,000 feet has
percent.
This means a 5.1-foot drop
been used.
The ground slope of 1
over the 75 feet. This would put the
percent is used and the minimum sewer
invert at manhole 8 about 5-1/2 feet
size of 6 inches is tried. The actual
(3.1 slope difference + 2 cover +
velocity is 2.83 feet per second. The
about
1/2-foot
pipe
width)
below
invert of the outflow sewer at manhole
ground.
The sewer would start this
8 must be at least 2.5 feet below
low
and
probably
go
lower,
ground level or at or below the invert
necessitating much excavation.
Thus
of the incoming sewer, whichever is
the better choice is to go to a 6-inch
lower. Therefore, 297.5 is used. The
house sewer which will allow a much
invert of the sewer at manhole 7 is 4
smaller slope.
The design with a 6-
feet lower or 293.5 feet.
The sewer
inch sewer is shown in row 2, figure
is sketched on the solution drawing,
17.
The invert elevation at the
figure
18.
The
only
difference
building had to be chosen.
It was
between the method used in the design
made to be 2-1/2 feet below the ground
of the lateral from MH 7-1 to MH 7 and
elevation.
This will allow 2 feet of
any of the previous ones is a slope of
cover over the 1/2-foot pipe.
Thus
4.55 percent instead of the ground
the invert is 302 - 2.5 = 299.5 feet.
slope of 4.5 percent.
This slight
The invert elevation at manhole 8 is
increase is due to going from 4-inch
then 299.5 less than the 2-foot drop
to 6-inch pipe at manhole 7-1.
An
in the pipe or 297.5 feet.
elevation of 302.6 less a ground drop
of 9 feet cannot be used because this
b. Connections to MH 7-1.
For the
would not provide 2.5 feet of ground
line from building B to MH 7-1, the
above the invert at the end of the
ground slope of 1 foot in 40 is tried
lateral. The data is shown in row 6.
Figure 18. Sample design solution (issued as separate item).
d. Main from MH 7 to MH 4. It can
available.
One would be to start as
be seen from the profile that the
above but increase the slope so that
sewer between MH 7 and MH 6 cannot be
sufficient cover can be had.
This
placed at the same slope as the ground
will necessitate deep excavation.
As
starting at the elevation of the inlet
an example, the dotted line in the
invert at MH 7.
If this were done
solution could be followed.
Another
there would not be sufficient cover in
solution is available, however.
That
the
center.
Two
solutions
are
is to drop the outlet of manhole 7 and
4-23