TM 5-688
C-9. Fluorescent and high intensity discharge (HID) lighting.
50 Hz. Derating is not recommended. Fixtures configured for 50 Hz should be purchased.
C-10. Motors.
a. 50 Hz. In general, derating a 60 Hz motor is not recommended. See chapter 3 for exceptions
b. Voltage. Derating for voltage is not recommended. Contact vendor to purchase appropriately configured equip-
ment, or use transformer to convert supply voltage to motor's rated voltage level.
C-11. Motor Starters.
a. 50 Hz. Derate by
multiplying 60 Hz
horsepower rating by
4/5 to
yield the 50 Hz
horsepower rating.
b. Voltage. Derating for voltage is not possible. Contact vendor to purchase appropriately configured equipment,
or use transformer to convert supply voltage to motor starter's rated voltage level.
C-12. Clocks.
a. 50 Hz. Derating is possible but meaningless since 60 Hz clock will not keep correct time in 50 Hz environment
b. Voltage. Derating for voltage is not recommended. Contact vendor to purchase appropriately configured clocks,
or use transformer to convert supply voltage to clock's rated voltage level.
C-13. Computer power supplies.
a. 50 Hz. Derating is not possible due to equipment construction. Contact vendor to purchase 50 Hz rated equip-
ment.
b. Voltage. Derating for voltage is not possible. Contact vendor to purchase appropriately configured equipment,
or use transformer to convert supply voltage to equipment's rated voltage level.
C-2